Installation in new or existing raised-floor data centers, to fill long narrow, above floor, perimeter cutouts.
Installation in new or existing raised-floor data centers, to fill long narrow, above floor, perimeter cutouts.
6" Extended: • One opposing overlapping array of 0.010" diameter upper filaments • One opposing array of 0.020" diameter lower filaments • 1550 filaments per lineal inch
Grommet filaments are premium grade Nylon 6 ensuring bristle flexibility, compliance, and self-sealing recovery. Filaments are conductive with static dissipation properties.
Grommet and filaments safely bleed off any static build up on cables passing through the cable opening caused by high velocity airflow (triboelectric effect). Grommet is an integral part of the raised floor’s static dissipation system, providing 1 GigaOhm of resistance.
Grommet shall achieve 100% bypass airflow sealing in areas undisturbed by cable penetrations at static pressures up to 0.10 inches of water column. When penetrated by four 1/2" cables, sealing is 100% effective at the static pressure required to cool up to 3 kW/cabinet with a 95% sealing effectiveness at a static pressure of 0.05". |
 Online Price: $98.80

|
Contact us for quantity pricing!
| Specifications |
| Overall Size (wxdxh)
|
24” x 9” x 3/4" |
| Height Above Raised Floor |
1/2" |
| Maximum Cut-out Sealed |
22" x 8" |
| Useable Cable Area |
22" x 5 1/2" |
| Product
PDF |

|
|